Submersible 3 - Core Flat Cables
Submersible 3 - Core Flat Cables Pump cables is a specialized product to be used for submersible pumps in a deep well. The area of installation is physically restrictive, and the environment is very hostile.Raj Ratan Submersible 3 - Core Flat Cables is designed and manufactured keeping in mind these factors to achieve the highest possible degree of reliability.
Three core Flat Cables are manufactured with bright electrolytic grade copper with special PVC compound framing the core and the covering for longer durability.
Note :
The strand diameter is nominal however, construction of conductor is design to satisfy the requirements of conductor resistance as per IS:8130:1984. *As per conductor class 2 of IS:8130:1984 **As per conductor class 5 of IS:8130:1984
3 Core Flat Cables as per IS:694:1990 with ISI mark

| Conductor | Insulation | Sheath Overall Dimensions | Conductor Resistance @20°C (max.)ohms/km. | Current Carrying Capacity @ 40°C (Amp.) | ||||
| Area (Nom.) Sq. mm. | No./size of Wires mm | Thickness (Nom) mm. | Core Dia. (Nom) mm. | Thickness (Nom) mm. | Width 'W' mm | Thickness 'T'mm | ||
| 1.5 | 22/0.3 | 0.8 | 3.25 | 1.15 | 12.5 | 5.8 | 12.10 | 14 |
| 2.5 | 36/0.3 | 0.9 | 3.90 | 1.15 | 14.4 | 6.3 | 7.41 | 18 |
| 4 | 56/0.3 | 1.0 | 4.65 | 1.15 | 17.2 | 7.4 | 4.95 | 26 |
3 Core Flat Cables generally conforming to IS:694:1990
| Conductor | Insulation | Sheath Overall Dimensions | Conductor Resistance @ 20°C (max.) ohms/km. | Current Carrying Capacity @ 40°C (Amp.) | ||||
| Area (Nom.) Sq. mm. | No./size of Wires mm | Thickness (Nom) mm. | Core Dia. (Nom) mm. | Thickness (Nom) mm. | Width 'W' mm | Thickness 'T'mm | ||
| 6.0 | 84/0.3 | 1.0 | 5.20 | 1.15 | 18.7 | 7.9 | 3.30 | 31 |
| 10.0 | 140/0.3 | 1.0 | 6.60 | 1.40 | 23.7 | 9.9 | 1.91 | 42 |
| 16.0 | 226/0.3 | 1.0 | 8.20 | 1.40 | 28.0 | 11.4 | 1.21 | 57 |
Selection Guide for 3 Core Flat Cables
1) HP Vs Current: The full load current for submersible pump motors, 3 phase, 50 cycles, 415~425 V.
| Hp | 5.0 | 7.5 | 10.0 | 12.5 | 15.0 | 17.5 | 20.0 | 25.0 | 30.0 | 35.0 | 40.0 | 45.0 | 50.0 | 55.0 | 60.0 | 65.0 | 70.0 | 75.0 | 80.0 |
| Amp | 7.5 | 11.0 | 14.9 | 18.9 | 22.5 | 25.2 | 28.4 | 35.6 | 42.3 | 50.4 | 58.1 | 62.1 | 67.5 | 73.8 | 81.0 | 87.3 | 93.6 | 100.80 | 108.0 |
2) Derating Factors: Multiply the current carrying capacity of the cable by factors given below for various ambient temperatures.
| Ambient Temperature C | 30 | 35 | 40 | 45 | 50 |
| Operating Factor | 1.09 | 1.04 | 1.00 | 0.95 | 0.77 |
Note:
- The number of wires is approximate and wire diameter is nominal they shall be such as to sat / DIN VDE 0295 / IS 8130 / BS 6360
- 4 core and 5 core flat cables are available on request.